摘要:廣州發電廠有限公司西村熱電廠1號鍋爐給粉機由YCT一160—4A滑差電動機改為TYPEY100一L1—4電動機及ACS 140(0.12~2.2 kw)變頻器控制后,在一次35 kV 系統外線路用戶側短路故障中。雖然繼電保護動作正確,但仍引起1號鍋爐滅火。通過對事件原因進行分析,得出合理的改進方法,從而對同類設備的設計與改進提出相關參考。
關鍵詞:鍋爐; 給粉機; 變頻器; 飛輪; 機械慣量
[b][align=center]Analysis of boiler flameout caused by an external line fault
ZENG Ling-jun,SHI Feng
(Ouangzhou Power Plant Co.,Ltd,,Guangzhou 51{}160,China)[/align][/b]
Abstract:The pulverized fuel feeder was changed from YCT-160—4A motor to TYPEY100一L1—4 motor and ACS 140(0.12~2.2 kW )transducer for Unit 1 boiler in Xicun Cogeneration Power Plant under Ouangzhou Power Plant Co,, Ltd.In an accident caused by the outside 35 kV feeder line short—circuit damage, though the relay—set acted correctly,the pulverized fuel feeder still caused flameout in the bo iler.This paper analyzes the accident and brings forward rational improving measures.which can be referenced in the design and improvement of similar equipment.
Key wolds:bo iler; pulverized coal feeder;transducer; flywheel;mechanicalinertia
廣州發電廠有限公司西村熱電廠1號鍋爐型號為WGZ220、9.8.13,于1989年5月投產至2003年底止,給粉機以前采用YCT160.4A滑差電動機進行調速給粉,其間多次遇到35 kV系統線路短路故障,從未引起1號鍋爐滅火。2003年底,1號鍋爐給粉系統改用變頻器調速及TYPEY100.L1—4電動機后,未很好考慮機械慣量的作用。改造后機械慣量過小,當35 kV系統外線路短路故障引起ACS140(0.12~2.2 kW)變頻器欠壓或瞬時失電停止輸出時(通過電試班模擬上述現象試驗給粉機變頻控制重起動正常),發現1號鍋爐給粉機轉速波動較大,影響給粉量,嚴重威脅1號鍋爐的安全運行。2005年4月30日,西村熱電廠發生一起由35kV系統外線路用戶側短路故障,導致西村熱電廠1號鍋爐滅火的故障,現將此次鍋爐滅火原因分析所得到的經驗教訓作一總結,以供參考。
[b][align=center]詳細內容請點擊:
一起由外線路故障引起鍋爐滅火的原因分析[/align][/b]